Phase control relay. Wire break monitoring and phase sequence. Setting of overvoltage, undervoltage, response delay. 220-460V AC

Phase control relay. Wire break monitoring and phase sequence. Setting of overvoltage, undervoltage, response delay. 220-460V AC
Product ID:

Main specifications

Function over voltage detectionДа
Function under voltage detectionДа
Phase failure monitoringДа
Phase imbalance monitoringНет
Phase sequence monitoringДа

Description

Lead-in distribution empty enclosuresare intended for electric power supply, accounting and distribution with 380/220 V voltage in three-phase AC networks (frequency - 50 Hz) as well as for protecting the lines at short circuits and overloads. They are also designed for often operation actuation and power-offs.

VRU metal empty enclosure is noted for its dismountable construction consisting of lateral frames installed on a base and connected with buckles. Lateral frames host a door, rear panel and top. Dismountable side panels help to reduce the expenses when assembling the empty enclosures into blocks. Cabling and wiring is organized below the empty enclosure.

Design Features

Specifications

Function over voltage detectionДа
Function under voltage detectionДа
Phase failure monitoringДа
Phase imbalance monitoringНет
Phase sequence monitoringДа
Supply voltage, В220...460
Voltage type for actuatingПеременный (AC)
Number of contacts as change-over contact1
Nominal current of contact groups at AC-1, А10
Max. cable cross section, мм²одножильный 1x2,5 или 2x1,5 многожильный с наконечникам 1x2,5
Error of measurements, процентов± 1
Degree of protection of IP front panelIP40
Height, мм95
Min. adjustable delay-on energization time, с0.5
Degree of protection of the IP terminalIP20
Range of frequency of supply voltage, Гц45...65
Max. permitted off-delay time, с10
Indicator of operation of the relayКрасный светодиод (R)
Max. permitted delay-on energization time, с-
Control error, процентов± 5
Mechanical wear resistance, циклов10^7
Rated control supply voltage Us at DC, В-
Mounting methodDIN-рейка (стандарт) 35 мм
Indicator of presence of voltageЗелёный светодиод (Un)
Min. adjustable off-delay time, с0
Electric wear resistance, циклов10^6
Depth, мм64
Hysteresis, процентов2
Weight, кг0,064
Burning positionЛюбое
MaintainabilityНет
Time of reaction, с(0,1...10) ± 10%
Ambient temperature, °C-20...55
Range of settings on voltage, процентов2...20
Rated control supply voltage Us at AC 50HZ, В220...460
Nominal voltage of contact group, В250 АС / 24 DC
Pollution degree2
Over voltage category3
Voltage measurement range, В176...552
Width, мм18
Type of voltage measurement rangeПеременный (AC)

Documents