Modular automatic transfer switch AVR-2 LITE 63A KARAT IEK

Product ID:
Main specifications
Nominal current, А | 63 |
Number of poles | 3 |
Switching Control Method | Ручное и автоматическое |
Breaking capacity (IEC947, Icu, 400 V), кА | 4.5 |
Operating voltage range, В | 160...265 |
Advantages
- Fixing the front panel without screws.
- Ready-made solution, no need to purchase a frame.
- Unlimited number of posts horizontally.
- Patented technology.

Specifications
Nominal current, А | 63 |
Number of poles | 3 |
Switching Control Method | Ручное и автоматическое |
Breaking capacity (IEC947, Icu, 400 V), кА | 4.5 |
Operating voltage range, В | 160...265 |
Lower threshold of ABP actuation voltage, В | 180 |
Upper threshold of ABP actuation voltage, В | 260 |
Switching modes | Авт. перекл. с авт.возвратом |
Width, мм | 248 |
Height, мм | 125 |
Type of built-in circuit breakers | ВА47-29 |
Overload protector, А | 63 |
Nominal voltage AC 50 Hz, В | 400 |
Moment of an inhaling of screws of contact clips, Нм | 2 |
Response characteristics from overcurrent type | С |
Availability of fire protection | Нет |
Number of handle operating positions | 3 |
Connection capability, мм² | 1...25 |
Mechanical design group in accordance with GOST 17516.1 | М2 |
Classification by ability to respond to short-circuit currents in accordance with GOST IEC 60947-6-1 | СВ |
Availability of relay for generator control | Нет |
Modular version | Нет |
Depth, мм | 125 |
Maximum number of conductors per clamp | ≤ 2 |
With ground fault protection function | Нет |
Type of conductors to attach | Провода и кабели с проведением специальной подготовки и шины |
Power consumption, Вт | ≤ 5 |
Operating temperature range, °C | -5...40 |
Documents
Passports