Catalog

Blog

15.04.2025
Assembling an electrical panel. Basic solution: CB + RCD

1.2.jpg

Many of our readers know how this or that device works individually. But when assembling an electrical panel, questions often arise: how to choose protective devices, how should they interact with each other and the load, in which regulatory documents is this mentioned? It is not always easy to find information on how to assemble an electrical panel from scratch, taking into account all the subtleties of selecting elements in combination.

In this article, we will discuss the nuances of assembling a basic electrical panel circuit with reference to real loads.

Initial data

Need to assemble a budget electrical panel for a one-story cottage with an area of 100 m2 with gas heating. The house has a three-phase supply, allocated power is 15 kW, the main circuit breaker for 32 A and the electricity meter are located on a pole.

Where to start?

Of course, with the technical assignment. Based on it, we will think through the overall assembly strategy, the circuit, and the correct operation of the protections. We have a floor plan with the location of sockets, lighting fixtures, and the electrical panel. We also know the equipment power and the location of household appliances.

3_Figure 1.png

Layout of sockets and switches in the room.

Task: select cables and protective equipment for a basic level panel.

Distribution into groups

What guidelines do we use?

SP 256.1325800.2016 "Electrical installations of residential and public buildings. Design and installation rules."

SP 256, clause 10.2 (distribution of loads into groups).

SP 256, clauses 15.28, 15.28 (norms for the number of sockets).

Let's designate the number of socket groups. As a rule, wiring accessories are grouped in relation to the room and the equipment located in it.

On our plan, we will delineate the socket groups, they are highlighted in different colors (see Figure 2).

7_Figure 2.png

Socket groups.

We will combine non-residential premises into one socket group: open and closed terraces and corridor (green color on the diagram). We will also assign two small bedrooms to one group (red color), and bring a separate group to the large bedroom (orange color).

The kitchen-dining room will also have its own line (blue color). We will divide the kitchen into several socket groups: work area (gray color), refrigerator (light blue color) and oven with hood (beige color).

For the bathroom, we also provide a separate group (highlighted in purple), for the boiler room – a line for the boiler (yellow color) and a line for sockets and the pump.

In total, there are 11 socket groups in the cottage.

Combining lighting groups

Our recommendations:

  • Provide at least two lighting groups.
  • Power supply for lighting fixtures should be separate from socket groups.
  • For each room, two types of lighting should be provided: general (ceiling lights) and local (wall, table, etc.).

In our case, we have identified 3 lighting groups (see Figure 3). We will combine lines for ceiling lights in non-residential areas into one group (highlighted in red on the plan). Another line will be for wall lights in living areas and corridor (green color). Another group – for ceiling lights in living areas (yellow color on the plan).

8_Figure 3.png

Lighting groups.

Load calculation

What guidelines do we use?

SP 256, Chapter 7.

Let's calculate the value of consumed power. Simply adding up the nameplate power of consumers is not possible: this way we will get an overestimated current value and extra costs.

Calculations can be made using formulas, based on the hourly maximum of consumed power using demand and utilization factors. We will use a table developed by IEK GROUP technical training specialists:

11_Panel assembly_1_1280x720.png

The power factor (cos φ) must also be taken into account. Usually this characteristic is indicated in the passport. For active loads, for example, an oven, cos φ is 0.95, and for consumers with motors, for example, a pump, it is 0.75. Therefore, if the same power is indicated in the passports, the consumed current may differ.

For simplicity of calculation, you can take cos φ = 0.9.

We recommend entering the results into a summary table for competent design of the electrical panel diagram. Below is an example of such a table with a breakdown by groups. Some information is still hidden.

9_Broadcast 1_CBRCD13 01 copy.jpg

Power consumption of equipment in the cottage.

We determine the total calculated power, it should not exceed the allocated power. Based on this, we select equipment. We can also calculate the total current. When further selecting the main circuit breaker, it must be taken into account that its rating must not be lower than the total current.

These values have already been entered into the table above.

Cable selection

What guidelines do we use?

GOST 31565-2012 (fire safety standards).

GOST R 50571.5.52-2011 (cable laying methods).

SP 256, Table 15.3 (cable cross-section selection).

When selecting a cable, the value of the continuous permissible current, which depends on a number of external conditions, is primarily important:

  • Method of installation (open, in walls, trays, ducts, etc.).
  • Presence of adjacent power circuits running nearby.
  • Ambient temperature.
  • Presence of current distortions by the load.
  • Load operating modes and starting current values.

Another important criterion is fire safety. For most groups, we choose VVGng(A) LS cable. The LS index means that when burning, the cable emits a minimum amount of smoke, so in residential premises it is necessary to use it.

For socket groups, we choose a copper cable with a cross-section of 3×2.5 mm2, for lighting circuits – with a cross-section of 3×1.5 mm2.

According to manufacturer data and GOST R 50571.5.52-2011, for a cross-section of 2.5 mm2, the permissible current under the worst installation conditions is 17.5 A. Therefore, the protective circuit breaker for such a cable (and hence for all socket lines) is selected with a rating of 16 A. According to the same principle, we select a circuit breaker for the lighting group: it should have a rating of 10 A.

We will connect the submersible pump with a cable with rubber insulation, type KG 3×1.5 mm2. From the outdoor pole to the electrical panel, the main cable VVGng(A) LS 4×10 in a HDPE pipe will be laid.

We enter the selected cables into the table.

10_Broadcast 1_CBRCD16- copy.jpg

Cable selection for organizing electrical wiring.

Selection of protection devices

The main rule for selecting circuit breakers – the rated current of the CB must be greater than the calculated load current, but less than the continuous permissible current of the cable.

In other words, the circuit breaker should not trip during normal operation of electrical appliances. At the same time, it should trip in case of an emergency current excess to prevent cable overheating.

We select circuit breakers taking into account the time-current characteristic (TCC). For most household loads, circuit breakers with TCC B and C are suitable. For LED lighting, we recommend installing TCC C, and for loads with high starting currents – D.

12_Panel assembly_2_1000x1000_2.png

Selection of circuit breakers depending on the time-current characteristic.

Selection of circuit breakers based on breaking capacity

What guidelines do we use?

GOST 32395-2020 "Distribution boards for residential buildings. General specifications", Clause 6.6.5.

We choose a circuit breaker with a breaking capacity of 6 kA for the input, and circuit breakers for outgoing lines will be chosen at 4.5 kA.

KARAT series circuit breakers VA47-29 and VA47-60M are suitable for us.

At this stage, our diagram takes on the following outlines:

4_Broadcast 1_CBRCD28- copy.jpg

Selection of circuit breakers.

Selection of residual current devices (RCDs)

What guidelines do we use?

SP 256: Appendix A, as well as clauses 10.2 and 10.13.

In all socket groups, residual current devices with a setting of 30 mA should be used. Also, SP 256 (clause A.4.15) requires installing RCDs with a setting of 10 mA on a dedicated line in showers, bathrooms or sanitary cabins.

It is necessary to take into account the conditional short-circuit current – the characteristic must be not less than the rated maximum breaking capacity of the circuit breaker installed in series. Also, the rated current of the RCD must be not less than the rated current of the circuit breaker.

Taking into account the selection of RCDs, the diagram looks like this:

5_Broadcast 1_CBRCD39- copy.jpg

Selection of residual current devices (RCDs).

We use KARAT series RCDs.

Load distribution

What guidelines do we use?

SP 256, clause 10.5.

When distributing loads across phases, the difference in currents of the most and least loaded phases should not exceed 30% within one electrical panel and 15% at the beginning of supply lines.

By simple summation of the calculated load currents per phase, we selected the optimal distribution:

6_Broadcast 1_CBRCD45- copy.jpg

Load distribution.

Phase A powers the gas boiler, lighting of the terrace, corridor, bathroom and boiler room, as well as the pump. In addition, phase A goes to the sockets of the terrace and corridor and to the sockets of the oven and hood.

Phase B goes to two socket groups in the bedroom, the water heater and the washing machine.

Phase C powers wall and ceiling lighting in the rooms, dining room sockets, kitchen work area and refrigerator.

Housing selection

We need a housing that will accommodate equipment for 26 modules. We recommend leaving space "in reserve" of 20–30%. Therefore, we choose the plastic housing of the TEKFOR series ЩРН-П-36 for 36 modules.

It is not worth saving on panel dimensions. First, free space facilitates air circulation. Secondly, you may later want to add other elements – voltage relays, contactors, spare groups.

Assembly

We connect switching devices using connecting busbars. We will also need a cross-module for distributing neutral conductors.

The neutral conductor goes from the main circuit breaker to the common busbar in the cross-module. Then the neutral goes from the common busbar to the residual current device. After the RCD, the neutral goes to separate busbars in the cross-module, the neutral conductors of consumers protected by the RCD will be connected to them.

For more details on assembling a basic level panel, see the video:

https://dzen.ru/video/watch/672375ebbe79a039be76f76c

Product information search

Selection and Purchase
Product Information
  • Product Card

    Карточки товара сформированы на всю продукцию IEK. Сведения размещены в online каталоге продукции: https://www.iek.ru/products/catalog/

    В карточках товара можно найти следующую информацию:

    1. Полное наименование и артикул продукции.
    2. Краткое описание.
    3. Фото.
    4. Технические характеристики.
    5. Сертификаты и отказные письма.
    6. Руководства по эксплуатации и инструкции по монтажу.
    7. Габаритно-установочные чертежи.
    8. Информационные материалы.
    9. Модели для проектирования.
    10. Особенности конструкции и комплектация.
    11. Логистические параметры.
    12. Совместно применяемые изделия.

  • Technical Support Consultation

    Контакты технической поддержки

    IEK:

    +7 (495) 542 22 27

    helptd@iek.ru 

    С 9-00 до 17-30 МСК, кроме выходных.


Product Support
Project Support
  • Analogue Selection
    Для подбора аналогичной продукции из ассортимента IEK Group, направьте заявку на электронную почту технической поддержки:helptd@iek.ru

    В заявке укажите свои контактные данные (город, наименование организации, номер телефона) и приложите список продукции, которую необходимо заменить. 
  • Lighting Calculation
    Для выполнения светотехнического расчёта в программе DiaLux, направьте заявку на электронную почту технической поддержки helptd@iek.ru 
    В заявке укажите свои контактные данные (город, наименование организации, номер телефона) и информацию для расчёта: параметры помещения (план помещения), высоту установки и тип светильников, требуемый уровень освещённости. 
  • Product Selection by Project
    Для подбора продукции по проекту или техническому заданию, направьте заявку на электронную почту технической поддержки: helptd@iek.ru 
    В заявке укажите свои контактные данные (город, наименование организации, номер телефона) и приложите необходимые документы. 
Service Support
  • Service Center Contacts
  • Service Issues
    При возникновении сложностей с сервисным обслуживанием обратитесь в техническую поддержку на электронную почту helptd@iek.ru 
  • Warranty Exchange and Return
    По вопросам обмена или возврата продукции по гарантии Вы можете обратиться в торговую организацию, у которой её приобретали. Рекомендуем обратиться в торговую организацию с письменной претензией с требованием обмена или возврата продукции по гарантии. Если продукция приобреталась физ. лицом, возможно обращение по гарантии к производителю. Для этого обратитесь в техническую поддержку на электронную почту helptd@iek.ru 
Information for Designers and Documentation
Didn’t find the answer?